What size equiment ground would you use for 200 amps when you up the wire size to 250 mcm for voltage drop

Checked on August 13, 2025
Disclaimer: Factually can make mistakes. Please verify important information or breaking news. Learn more.

This fact-check may be outdated. Consider refreshing it to get the most current information.

Was this fact-check helpful?

1. Summary of the results

Based on the analyses provided, for a 200-amp service using 250 MCM wire sized up for voltage drop, the equipment grounding conductor size follows specific NEC requirements:

  • Base requirement: According to NEC Table 250.122, a 200-amp circuit requires a #4 AWG copper or #2 AWG aluminum/copper-clad aluminum equipment grounding conductor [1] [2] [3]
  • Proportional sizing rule: Since the ungrounded conductors (250 MCM) are increased in size for voltage drop considerations (not for ambient temperature corrections, conductor fill, or adjustment for more than three current-carrying conductors), the equipment grounding conductor must be increased proportionally [1] [2] [3]
  • Practical application: One analysis specifically addresses a similar scenario with a 250-foot run from a 400-amp pedestal to a 200-amp shop, recommending #2 aluminum grounding wire when using 250 kcmil aluminum conductors, or #1 aluminum if conductors are bumped up to 300 kcmil [4]

2. Missing context/alternative viewpoints

The original question lacks several critical pieces of information that affect the final answer:

  • Wire material specification: The question doesn't specify whether the 250 MCM wire is copper or aluminum, which significantly impacts the proportional calculation [1] [2]
  • Installation conditions: The analyses show that ambient temperature corrections, conductor fill, or adjustments for multiple current-carrying conductors would not require proportional upsizing of the equipment ground [1] [2] [3]
  • Specific voltage drop percentage: While voltage drop is mentioned as the reason for upsizing, the target voltage drop percentage isn't specified, which could influence the final wire selection [5]
  • Run length: The distance of the circuit run is not provided, though this is crucial for voltage drop calculations [4] [5]

3. Potential misinformation/bias in the original statement

The original question contains no apparent misinformation or bias, but it is incomplete in its technical specifications. The question appropriately recognizes that:

  • Wire size may need to be increased beyond minimum ampacity requirements for voltage drop considerations
  • Equipment grounding conductor sizing may be affected by this increase

However, the question would benefit from specifying the wire material, installation conditions, and target voltage drop percentage to receive a precise answer. The analyses confirm that the NEC does require proportional upsizing of equipment grounding conductors when ungrounded conductors are increased for voltage drop purposes [1] [2] [3].

Want to dive deeper?
What is the maximum voltage drop allowed for a 200 amp service?
How does the National Electric Code (NEC) determine equipment ground size?
What are the benefits of upsizing wire to 250 mcm for a 200 amp service?
Can a 250 mcm wire be used for both equipment grounding and neutral conductors?
What are the differences between copper and aluminum wire for equipment grounding in a 200 amp service?